50 psf of snow is Massachusetts. Not here.

S = C_b·Ss + Sr, with YOUR town’s Ss and Sr.

Nearly every timber-framing book in circulation is American. Their example frames are designed for 50 psf of snow — 2.39 kPa. That is western Massachusetts. Cape Cod is 25 psf; the Rockies, over 200.

In Quebec the load is calculated: S = C_b·Ss + Sr. S is the snow load the roof must carry, in kPa. Ss is the ground snow load that returns once in 50 years in your town; Sr, the rain load that adds to it, same return period. Both are read from appendix C of the 2020 NBC, in kPa. C_b is the roof factor, the share of the ground snow that stays on the roof: 0.55 — or 0.45 if your roof is 4.3 m wide or less, which covers many small buildings.

Your email to open the designer

Because your frame is saved under your email, and that is where your set will be delivered.

Taking 2.0 kPa as a default underestimates by 30 to 48 % as soon as you leave Montreal.

What it hits first: rafters and plates. No rafter, plate or tie-beam section from an American book carries over unchanged. The calculation has to be redone.

The designer asks WHERE you are building: it reads your town’s Ss and Sr from the code, applies the C_b for your roof, and sizes with that. If your town is not listed, you enter your own snow load.